滲漏報(bào)警器是用于油浸式電力變壓器用復(fù)合管式水冷卻器發(fā)生滲漏故障時(shí)發(fā)出報(bào)警信號的裝置。
Hence the seepage enunciator is the device that issues the alarm when being used oil the soaking type power transformer type water-cooling with the multiple-unit tube but ware to occur the seepage to hinder
1.型號含義 1. The model meaning
L B 0 2
第2次設(shè)計(jì) 2nd design
報(bào)警器 Enunciator
滲漏 Seepage
2.工作條件
2. The work condition
2.1.工作環(huán)境溫度0℃~55℃。
2.1. 0℃~55℃'s work environment
temperature.
2.2.當(dāng)空氣溫度為25℃時(shí),
濕度不大于90%。
2.2.When the air temperature degree
is 25 ℃s high above in the sky ,
humidity is not very in 90%.
2.3.海拔高度不超過2000米。
2.3. The elevation height does not surpass 2000 meters.
2.4.周圍無劇烈震動(dòng)和顛簸的場所。 圖1
2.4. Surrounding inacute shake and place jolting. The picture 1
3.技術(shù)參數(shù)
3. The technology parameter
3.1.產(chǎn)品外形尺寸:φ76×140。
3.1. The product OAD : φ76×140.
3.2.產(chǎn)品重量:1.5㎏。
3.2. Product weight : 1.5㎏.
3.3.滲漏液體容積為不超過50㎝3時(shí)報(bào)警。
3.3. The seepage liquid volume is at 40 o'clocks to report to the police.
3.4.接點(diǎn)容量:220V,AC 3A,DC 0.5A。
3.5.The contact capacity:220V,AC 3A,DC 0.5A.
4.結(jié)構(gòu)特點(diǎn)和工作原理
4. Structure characteristic and work principle
4.1.本產(chǎn)品由法蘭、殼體、浮筒、永久磁鐵、隔板、干簧接點(diǎn)開關(guān)、接線盒等組成。參見圖1。
4.1. This product is by flange and shell aspect , float , permanent magnet , screen and dry reed contact open Guan forms by the wiring box etc See also the picture 1.
4.2.當(dāng)冷卻器發(fā)生滲漏時(shí),滲漏的液體流到殼體中,當(dāng)滲漏的液體達(dá)到一定容量時(shí),浮筒上升并帶動(dòng)永久磁鐵上升,使干簧接點(diǎn)開關(guān)動(dòng)作發(fā)出報(bào)警信號。
4.3.The liquid of seepage flows into the shell aspect when the chiller occurs the seepage , and when liquid when the seepage achieves the fixed capacity , the float moves upward and drives the permanent magnet moving upward , and makes futilely reed contact open close the action and issue the alarm Installation.
5.安裝
5. Installation
5.1.安裝尺寸參見圖1。
5.1. Installing the size sees also the picture 1.
5.2.滲漏報(bào)警器應(yīng)安裝在復(fù)合管式水冷卻器的水管和油管之間的空腔的下部,這樣可使水管滲漏的水和/或油管滲漏的油能順利地流到滲漏報(bào)警器中。
5.2. The seepage enunciator should be installed in the multiple-unit tube type water-cooling but lower part of cavity betwee